AT&T DEFINITY 2500 series Manuel d'instructions Page 168

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 223
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 167
ENVIRONMENTAL REQUIREMENTS
With Multicarrier Cabinet(s)
A fully-loaded multicarrier cabinet (five carriers) dissipates approximately 8000 BTUs per hour.
However, the typical average dissipation for a cabinet of three carriers is 5000 BTUs per hour.
With Single-Carrier Cabinet(s)
A stack of four single-carrier cabinets (fully loaded) dissipates approximately 6700 BTUs per
hour. However, the typical average dissipation for a one-carrier system is 1700 BTUs per hour.
Table AL shows the typical average and maximum system power consumption and also the sys-
tem heat dissipation for different size SCC and MCC systems.
TABLE AL. System Power Consumption and Heat Dissipation
System Power Consumption
System Heat Dissipation
(Volt-Ampere Rating)
(BTU per Hour)
SCC MCC SCC
MCC
Size
Avg Max Avg Max
Avg
Max
Avg
Max
Tier 1
540 760 540 760 1700
_ _ _
Tier 2
1080 1376 1080 1376 3400
_ _ _
Tier 3
1620 1976 1620 1976 5100
_ _ _
Tier 4
2160 2584 2160 2584 6700
_ _ _
Tier5
_ _
2700 3344
_ _
5000 8000
158